top of page
IMG_7825.jpg

Lighting supply coming off a socket with a three core flex 

IMG_7826.jpg

Not enough sockets in locations and non fused extension devices being used 

IMG_7817.jpg
  • Copper cores twisted together and taped up 

  • Non UV cables being used to supply garage 

IMG_7810.jpg

Non IP rated light in wet area 

IMG_7814.jpg
  • Single core cables exposed 

  • Non IP rated socket in garage 

  • No RCD protection on sockets 

IMG_7815.jpg

Non UV cable being used to supply outside light 

IMG_7823.jpg

Socket has been damaged and signs of burning 

79853535-812E-44D3-BB8E-5164A3B159C7.jpg

RCD unit has failed its test button and no RCD protection across the DB 

IMG_7824.jpg
  • Non IP rated light in a bathroom 

  • No RCD protection in bathroom 

IMG_7820.jpg

Neon on sockets not working, indication off position 

IMG_7813.jpg

Junction box damaged and tapped back together 

IMG_6707_JPG.jpg

Make shift junction box, exposed live parts 

IMG_7812.jpg
  • Copper cores twisted together and taped up 

  • Non IP rated light in wet area 

IMG_7819.jpg
  • Non UV cables being used to supply outside lights 

  • Water damage in light 

IMG_7809.jpg
  • Non IP rated socket in wet area 

  • No RCD protection on garage sockets with a TT earthing system

  • Non IP rated light in wet area 

8A1F5E8E-FD87-42C7-9C39-69F0AEBBEDBC.jpg
  • DB is made up of combustible material 

  • No RCD protection 

  • No surge protection 

IMG_7829.jpg

Junction box with a flex cable coming out into a hard wired socket 

IMG_7818.jpg
  • Non UV cables being used to supply outside lights 

  • Copper cores twisted together and taped up

  • Live exposed ends coming out of the bottom of the light

IMG_7822_edited.jpg

Not enough sockets in locations and non fused extension devices being used 

IMG_7811.jpg

Live exposed cables bundled up in a garage 

IMG_7821.jpg

Socket has been damaged and signs of burning 

IMG_7811.jpg
  • Bundle of unsafe live cables with exposed live ends 

  • Junction box damaged and tapped back together 

IMG_7827.jpg
  • Extension cable has had the plug top cut off and hard wired into the circuit 

  • The flex has been cut and jointed to extend a supply using twisted cores and tape 

bottom of page